Thermal Energy Storage Systems

Novus Thermal Energy Storage (TES) tanks are ASME Section VIII, Division 1-engineered pressure vessels designed for chilled-water thermal energy storage in mission-critical data centers, central plants, and industrial process cooling applications. Every vessel carries the ASME U-Stamp and National Board registration as standard.

Product Description

Novus TES tanks are engineered around the challenge of thermocline preservation – maintaining a sharp thermal gradient between warm return water and cold supply water to maximize usable storage capacity. Custom internals are standard on every vessel, not an upgrade. CFD-verified thermal performance is performed before fabrication release.

The product line spans three tiers: packaged emergency cooling systems for small data center nodes; modular systems for commercial data centers and central plants; and large central plant systems for hyperscale campuses and district cooling.

Vessels are designed for outdoor exposed, aboveground installation. Insulation, structural anchorage, seismic design, and freeze protection are engineered in from the start.

Technical Specifications

  • Design Code ASME Section VIII, Division 1 - U-Stamp on all sizes
  • National Board Registered - Form U-1 provided with every vessel
  • Design Pressure 150 PSIG standard; 300 PSIG available and up to 1440 PSIG
  • Shell Material ASME SA-516 Grade 70 carbon steel
  • Internal Stratification Type 316/316L stainless steel engineered diffusers - shop-welded
  • Stratification Efficiency Minimum 90% per AHRI Guideline T at design conditions
  • CFD Verification Performed for all vessels above 1,000 gallons - PE-reviewed, pre-fabrication
  • Ton-Hour Range 5 to 300+ ton-hours depending on configuration (16°F design delta-T)
  • Hydrotest 1.3 times MAWP per ASME UG-99(b), current edition
  • Insulation Closed-cell polyurethane / polyisocyanurate, R-12 minimum, aluminum jacket
  • Exterior Coating SSPC-SP10 blast / epoxy primer / epoxy intermediate / urethane finish - 11 mil min DFT
  • Fabricated Odessa, TX and Troy, TX

Representative Applications

Mission-critical data center chilled water systems - N+1 chiller restart thermal buffer

Hyperscale data center campus thermal energy storage

Hospital and healthcare critical cooling - emergency thermal buffer

District cooling peak shaving and utility tariff demand response

Industrial process cooling - thermal buffer for variable load applications

Campus chilled water plants - multi-building TES